세관에서의 증발열전달 특성연구

박경수, 방광현 · 대한설비공학회 학술발표대회논문집 · 2002

The evaporating heat transfer of R-22 in small round tubes has been experimentally studied to investigate an effect of tube material. The experimental apparatus consists mainly of a refrigerant pump, a condenser and a receiver, a visual tube, two test sections of 300 ㎜-long brass and aluminum round tubes, a preheater for control of refrigerant quality at the inlet of test section. The heat flux is provided by heating wire wound on the outer wall of the test sections. A set of five thermocouples are embedded at the wall of the test section to measure the wall temperature. For refrigerant mass flux of 300 and 600 ㎏/㎡s, the inlet quality is varied from 0.0 to 0.9 and the wall heat flux is varied from 10 ㎾/㎡ to 20 ㎾/㎡. The measured evaporating heat transfer coefficients in the ranges of the present study are 2000~6000 W/㎡K, and the tube material showed negligible effect on the heat transfer coefficient.

Cited by 0 works.