카타플라스마(파스) 제조시설의 공조설계 및 시공유의점

유경록, 김세환, 박승태 et al. · 대한설비공학회 하계학술발표회 논문집 · 2010

In the air-conditioning system of the cataplasma(patch) manufacturing facility, the key point is to satisfy the basic GMP facility standards and prevent the smell from spreading to another rooms by removing efficiently the undiluted solution that is used on making the patch. So, the local exhaust will be carried out to save the energy consumption, not the total exhaust. And the differential pressure will be designed for air to flow from the corridor to the production area. Also, before the exhaust air goes out, the air should be conditioned through the absorption tower.