저가격 고 신뢰성의 병렬 운전 제어 기법
정석언 · 전력전자학술대회논문집 · 2007
In this paper, a low cost and high reliability control scheme is proposed for 400㎐ UPS system operated in parallel. The proposed control scheme is consisted of two parts which are synchronization and load sharing control. The synchronization control is achieved by discrete logic ICs and analog circuit. The load sharing control is realized by current transformers (CTs) without any controller. Therefore, This proposed control scheme is rather simple and the cost may be decreased, compared with control scheme using expensive controller such as DSP and CAN. The practical feasibility of the proposed control scheme is proved by analysis and simulation.
Cited by 0 works.