배전급 고온초전도 한류기 절연설계 최적화 연구

석복렬, 강형구, 이찬주 et al. · 대한전기학회 학술대회 논문집 · 2006

In this study, superconducting coil arrangements and cryostat concept design were conducted for the development of 13.2㎸/630A bifilar winding type high temperature superconducting(HTS) fault current limiter(FCL) with YBCO coated conductor(CC) wire. The coil consists of several layers with unique non-inductive solenoid winding method. Six types of HTS coil arrangements were investigated for the optimal insulation design of HTS FCL. And, conceptual design of cryostat was conducted for the decrement of thermal invasion and the prevention of low voltage insulation breakdown in the LHe which is used as pressurization gas in sub-cooling condition of liquid nitrogen(LN2). As the results, it was found that the modified suspended type cryostat with horizontal coil arrangement is beneficial to the insulation design of 13.2㎸ level bifilar winding type HTS FCL.

Cited by 0 works.

Authors