도류벽 형태에 따른 정수지 내 유동 특성과 소독능 변화에 대한 수치 해석적 연구

이석원, 박준정, 리광훈 · 대한설비공학회 학술발표대회논문집 · 2006

The SWTR(Surface Water Treatment Rule) requires achieving removal 99.9% Giardia and 99.99% Virus. To remove Giardia and Virus, disinfection process is essential process. CT is important index for Disinfection performance. CT value is expressed by C×T. C is represented by disinfection concentration and T is represented by T₁? which means 90% contact time in clearwell. To improve Disinfection performance, it is desirable to increase T₁?. Primary factor affected T₁? is flow pattern. Because guide wall change that flow pattern is uniform,, we have installed guide wall to increase T₁?. In this paper, we have performed numerical analysis for clearwell installed symmetric guide wall and center divided guide wall using CFD. We have analyzed flow pattern and T₁? in each clearwell. And, we compare symmetric guide wall with center divided guide wall in flow pattern and T₁?.