전체환기 모형실을 이용한 냉/난방 급기조건에서 환기방식별 환기효율 특성에 관한 연구
이재근, 구재현, 한정균 et al. · 대한설비공학회 학술발표대회논문집 · 2001
The objective of this research is to analyze the ventilation effectiveness in the non-isothermal air supply using mixing and displacement ventilation systems for indoor air quality control and management. In this study, a ventilation effectiveness is evaluated in a simplified model chamber using a tracer gas technique of CO₂ gas injected into a supply duct as a function of ventilation rates, supply/extract sites and cooling/heating air supply. The ventilation effectiveness decreased with increasing ventilation rate on the cooling and heating conditions. And the ventilation effectiveness of case 3(down supply and upper extract) was better than that of case 1(upper supply and upper extract) and case 2(upper supply and down extract) with the cooling supply conditions. But for the heating supply air conditions, the ventilation effectiveness of case 2 was better than that of case 3 and case 1.
Cited by 0 works.