오일 쿨러의 열전달 성능에 관한 실험적 연구
조동현, 임태우 · 대한기계학회 춘추학술대회 · 2008
The experimental study was carried out to evaluate the heat transfer performance on the shell side of shell-and-plate finned tube heat exchanger with three different tube numbers(9, 13 and 19). Oil flowing on the shell side was cooled by cold water flowing inside the tubes. A shell-and-tube heat exchanger of an oil cooler consisted of one shell pass and two tube passes with the inner tube diameter of 8.82 ㎜ and the tube length of 575㎜. Mass flow rate was varied from 1.2 to 6.0 ㎥/h for oil and from 0.6 to 3.0 ㎥/h for cold water, respectively. From the experiment of shell-and-plate finned tube heat exchanger, the shell side heat transfer coefficient of heat exchanger with 9 tubes was compared with that of 13 and 19 tubes. It was found that the heat exchanger with 9 plate finned tubes showed more performance of heat transfer than that of 13 and 19 tubes.