二重바닥溫突시스템 개발을 위하여 熱的 特性의 比較에 관한 實驗硏究
여한승, 김난행, 손장열 · 대한건축학회 논문집 - 계획계 · 2004
The aim of the research was to develop the double floor Ondol system. Experiment on radiant property, distribution of surface temperature, insulating ability for wet hydronic Ondol and double floor hydronic Ondol system was undertaken through physical experiments in a laboratory setting. Hot water whose temperature was varied from 40℃ to 60℃ with 10℃ interval was supplied to each Ondol system. As a result, (1) As for the heat loss from the floor to the underground, the Hydronic Radiant Floor Heating System with the Double Floorings was lower than the typical Ondol system. (2) Under consideration of the differences from supply water temperature to return water temperature, Hydronic+ Radiant Floor Heating System with the Double Floorings was higher than the typical Ondol system by 0.23℃ to 0.62℃ with regard to the heat storage of the Ondol structure. (3) When supplying the 60℃ hot water, heat radiation efficiency of the Hydronic Radiant Floor Heating System with the Double Floorings was higher than the typical Ondol system by 9.4% with regard to the heat storage of the Ondol structure.
Cited by 0 works.