태양열 제습냉방 시스템 제습탑 하단부 구조에 따른 압력강하 및 공기 유동 특성 평가

최휘웅, 박수봉, 손창효 et al. · 한국태양에너지학회 춘계학술발표회 논문집 · 2015

Traditional dehumidifier in solar desiccant cooling system has wall that is vertical to the direction of inlet air, so the air is blowout after congesting. But if the wall on the way of flowing air has inclination, air can flow smoothly. So, in this study, the simulation that evaluating pressure drop and air flow characteristic with bottom structure of dehumidifier is conducted on the three inlet air velocity conditions(1.5m/s, 2.0m/s 2.5m/s) with the three cases of slope angles(45 ,? 60 ,? 75 )? that the wall on the way of flowing air and two cases side angles(75 ,? 90 )?. Air flow characteristic result in congesting and decrease of velocity when it flow in traditional or vertical wall, but the congesting and decrease of velocity is decreased when the wall or side has a slope. Pressure drop was also decreased when the wall or side has a slope. In case of prototype(slope angle 40.60 ,? side angle 59.74 )?, the pressure drop shows lower value than traditional dehumidifier from 3 to 6 times then the improvement of dehumidification performance is expected by changing bottom structure.

Cited by 0 works.