지역난방 지역의 공동주택 단위면적당 에너지 사용량 분석
박재홍, 김삼열 · 한국태양에너지학회 춘계학술발표회 논문집 · 2014
It was started to supply the district heating system in Jwa-dong, Busan since May, 1996. In this study, it was analyzed to compare a unit heating load of thermal load standard and an actual energy usage from 2008 to 2012 for 23,355 apartment houses. An actual energy usage presented a great contrast to apartment houses above 100㎡ of the unit area and the percentage of the maximum gap was 33%. In the results, we could know that the heating area increase, the energy usage per unit area lower. The existing standards of unit heating load can not reflect actual condition. Because it uses the standards of heating facility made in the 1990's in spite of the changes of architectural plan, outside temperature and energy saving design standards of buildings. Also, the unit heating load provided Korea district heating corporation is presented to subdivide the heating area from 33㎡ to 60㎡ ,but the unit heating load above 60㎡ of heating area is the one value. In the result for analysis about Jwa-dong, the heating area of apartments ranged from 90㎡ to 100㎡. It was shown the necessity of subdivision for heating area of unit heating load. It is the time of wasting energy in the present situation by selection of excessive capacity for equipment and pipes. If the design standards of existing district heating system are improved, it can bring the effects about optimal capacity of equipments, saving of construction expenses and energy effectiveness.