조적 상단의 공극 유무에 따른 철근콘크리트 채움벽골조의 거동 비교
김충만, 유은종 · 대한건축학회 학술발표대회 논문집 · 2015
Masonry infills, which are used as partition wall, are generally regarded as nonstructural components, thus, only their weights are considered but their role as the force-resisting-components are ignored in structural design. However, the structural tests or earthquake damage evaluation at the other countries reveals that the behavior of masonry-infilled frame structures are significantly different from those of bare frame structures due to the influence of masonry infills.In this study, material testing and infilled frame test, when the thickness of masonry were varied as 0.5B and 1.0B respectively, were conducted and compared. A total of 5 frame specimens were tested, which included bare frame(BF), fully infilled frame(FIF) with the thickness of 0.5B and 1.0B(with and without silt for each case), and two partially infilled frames(PIF). Test results showed that the 0.5B and 1.0B FIF without slit have 182% and 291% of ultimate strength comparing with BF. Deformation capacity of such specimens were 71% and 23% of BF. In the case of FIF with slit, ultimate strength were 143% and 231% in ultimate strength, 64% and 47% in deformation capacity. Obtained test results were compared with the results of analytical study previously proposed to model the behavior of infilled frames.