판형 열교환기식 제습기의 제습 성능에 관한 실험적 연구

전동순, 문지현, 김영률 et al. · 대한설비공학회 2014년도 하계학술발표대회 · 2014

In this study, experimental investigations have been carried out to examine the dehumidification performance of plate heat exchanger type dehumidifier. LiCl aqueous solution is employed as a working fluid. The velocity and relative humidity of process air were selected as experimental variables. Effects of experimental variables on the dehumidification rate and effectiveness of dehumidification have been examined. As results, dehumidification rate increases with an increase in velocity and relative humidity of process air, but effectiveness of dehumidification decreases. The dehumidification rate was about 7.4 ∼ 23.8 g/min and effectiveness of dehumidification was 23 ∼ 49%.

Cited by 0 works.