지역난방 2차측 유량변화에 따른 실내온도 변화 및 에너지 사용량 분석

최상호, 홍성기, 조성환 et al. · 대한설비공학회 2013년도 하계학술발표대회 · 2013

The presented experimental analysis shows that the effects of flow rate of the secondary side of DHS(District Heating System). The results show that increasing flow rate in the secondary side of DHS decreases energy consumption and time to reach set-point of the heated room. The major finding for this effect is that when flow rate increases the overall heat transfer rate of radiant floor also increases. However, the results also show that the overall heat transfer rate is not lineally increased. So, this results show that there is an optimal flow rate for the secondary side of DHS. So, a further study should be conducted on heat flux rate changes with various flow rate in the radiant floor. It is also understood that the control of the radiant floor with hot water could be done more effectively with a combined control strategy including heat flux and temperature set-point. This experimental analysis has been performed using a lab scaled DHS pilot plant located in Jeonju University in Korea.