비등온 급기조건에서 환기방식에 따른 환기효율 특성에 관한 연구
이재근, 강태욱, 윤석구 et al. · 설비공학논문집 · 2001
The objective of this research is to analyze the ventilation effectiveness in the non-isothermal air supply using mixing and displacement ventilation systems for indoor air quality control and management. In this study, a ventilation effectiveness is evaluated in a simplified model chamber using a tracer gas technique of CO₂ gas injected into a supply duct as a function of ventilation rates, supply/extract sites and cooling/heating air supply. The ventilation effectiveness decreased with increasing ventilation rate on the cooling and heating conditons. And the ventilation effectiveness of case 3 (down supply and upper extract) was better than that of case 1 (upper supply and upper extract) and case 2 (upper supply and down extract) with the cooling supply conditions. But for the heating supply air conditions, the ventilation effectiveness of case 2 was better than that of case 3 and case 1.
Cited by 0 works.