복합시설 내 하이브리드 냉방설비의 열원단가 기반 최적 운전 알고리즘의 개발
권한솔, 하대웅, 허정호 et al. · 대한설비공학회 하계학술발표회 논문집 · 2007
Using cooling load forecast through such a new equation of regression, this study deduced and determined an algorithm that can determine energy input timing and operating durationfor each refrigerator according to lapse of time by allowing for each refrigerator’s characteristics like unit cost of heat source production and energy production methods. It is estimated that the hourly energy saved through this algorithm will amount to800 MJ/h equivalent to 10% of maximum gross energy production, with return on investment (ROI) expected to reach US 2,000$ a day. In the future, it is expected that a more precise forecast equation will be deduced by introducing extra variables (solar radiation, wind velocity) of outside air conditions, and such an advanced forecast equation will be usefully applied as a critical index in terms of building maintenance and LCC.
Cited by 0 works.