송전용 애자의 장기실증시험 분석

최인혁, 최장현, 정윤환 et al. · 한국조명·전기설비학회 학술대회논문집 · 2004

Experimental equipments for long-term outdoor tests of EHV insulators in outdoor were constructed. The testing insulators have been energized with 89 [kV] phase-to-ground AC voltage under identical condition at station, and the investigation was carried out for leakage current and various environments such as temperature, relative humidity and wind velocity. The test results of leakage current wave trends have forms on distorted waves including harmonics. The porcelain and glass insulators have low leakage current in case of daytime because moisture and humidity have relative low values. In comparison with these condition, high leakage current was shown at dawn and rainy day due to high humidity. However, leakage current of polymer insulators was shown approximately 120 [μm] without rotation to the weather due to hydrophobicity on their surface.