급기각도가 사무실 공간의 냉방 및 난방 성능에 미치는 영향
김묘선, 김영일, 정광섭 · 대한설비공학회 학술발표대회논문집 · 2009
Effect of angle of supply air on cooling and heating performances of office space is studied by numerical simulation. For a constant air volume(CAV) air-conditioning system, air is supplied vertically(90°) and horizontally(10°). Due to buoyancy, the supply angle affects the performance of cooling and heating. In cooling, since the cold supply air tends to move downward due to its high density, horizontal supply angle is better for uniform temperature distribution. In heating, however, vertical supply angle is preferred for better mean and uniform temperature distribution.