전위분포특성을 이용한 접촉전압과 보폭전압의 분석
이복희, 정현욱, 최종혁 et al. · 대한전기학회 학술대회 논문집 · 2006
This paper describes touch and step voltage in the reinforced concrete and steel poles. Ground surface potential rises were measured as a function of the separation between pole and ground rod. Touch and step voltage are calculated on the basis of the distribution of ground surface potential rises. As a result, touch and step voltages strongly depend on the position of installation of ground rod.