영상전류 측정을 이용한 부재수용가의 전기설비에 대한 안전확보 방안
林庸培, 裵錫銘, 金榮錫 et al. · 전기학회논문지 P · 2006
A electrical fault that may generate an electrical disaster is defined as any abnormal condition caused by reduction in the insulation strength. To find out the abnormal condition, periodical inspections have being performed every 3 years. Recently, the number of empty houses during normal working hours is rising by dramatic increase in the number of nuclear families and double income families. To define the potential risk of the electric installation, measurement of zero phase current has been being considered, But the measured value could not be adapted to an absolute reference to the installation because the measured zero phase current value also contained capacitive leakage current. Therefore, in this paper, the correlation between the condition of the electrical installation and the zero phase current was analyzed, The result focuses on to detect them in a cost efficient way.