이산화탄소 냉매용 전자팽창밸브의 유량 특성
황윤욱, 김욱중 · 대한설비공학회 하계학술발표회 논문집 · 2007
This study investigated the mass flow rate of carbon dioxide through electronic expansion valves (EEVs) whose orifice diameters of EEV are 1.6 mm and 1.8 mm. The mass flow rates were measured at various EEV inlet temperatures and pressures for several EEV openings. The EEV inlet temperature was varied from 10℃ to 40℃ at the EEV inlet pressure of 8 MPa and 10 MPa, respectively. The mass flow rate of carbon dioxide through the electronic expansion valves ranged from 50 g/s to 120 g/s. The EEV opening and the density around critical point affected the mass flow rate of carbon dioxide. Empirical correlation based on Buckingham ?-theorem was developed and expected the experimental data within an average absolute deviation of 5.4%.