Wilson Plot Technique을 이용한 열전달계수의 측정

권정태, 배성원, 김무환 · 대한설비공학회 학술발표대회논문집 · 1997

Single phase heat transfer coefficients were measured for turbulent water flow in a short annulus by using Wilson plot technique. The Reynolds numbers were 2,000~10,000. It was difficult to find any recommendable heat transfer correlation available for our experimental cases. In this range, therefore, a short annulus was tested as a countercurrent heat exchanger in order to. obtain convective heat transfer coefficients. The heat transfer coefficients were proportional to Re^(0.68) for the short annulus in the Reynolds number range 2,000~10,000.