고온 및 저온공기의 풍량 제어에 의한 실시간 공기 온도 제어
장영수, Younggy Shin, 김영일 et al. · 대한설비공학회 학술발표대회논문집 · 2000
In this study, an air conditioner system for real time control was proposed. The system is composed of heating loop, cooling loop, and a mixing box. Heating and cooling loops controlled by PWM heaters supply hot and cold air to the mixing box. Mixing box where the hot and cold air mix has air flow sensor, control valve, and a temperature sensor. The discharged air temperature and mass flow rate are controlled by mass flow rate variation of hot and cold air. Feedforward-feedback controller combined with cascade control has been developed for multiple-input/multiple-output control. The performance test of this controller showed that air temperature and flow rate reach the setting values within 5 seconds.
Cited by 0 works.