열펌프 압축기 액분사 효과에 대한 실험적 연구

김선식, 방광현 · 대한설비공학회 하계학술발표회 논문집 · 2002

An experimental investigation on the effect of refrigerant liquid injection into the heat pump compressor on the system performance has been carried out. The heat pump in the present study is designed to draw heat from sea water and equipped with a 3-hp reciprocal compressor. The compressor head cover and valve plate has been machined to accomodate two 0.58 ㎜-I.D. injection nozzles. When the liquid injection mass is increased up to 7.2% of the refrigerant mass in the cylinder, the discharge gas temperature drops by 39 K. The liquid injection causes the rise of condensing pressure and accordingly compressor power. The COP, however, increases slightly and then decreases, indicating an optimum injection rate.

Cited by 0 works.

Authors