고체절연 부하개폐기의 부분방전 원인 분석
박찬용, 이도훈, 강원종 et al. · 대한전기학회 학술대회 논문집 · 2010
In this paper, we analyzed the cause of PD occurred in the Solid insulated Load Break Switchgear (S-LBS). The PD pulse generated by void, ground fault and corona was measured by coupling capacitor. The DIV (Discharge Inception Voltage), phase and pulse magnitude were used for analysis and classification.