다단 팽창장치의 영역별 유량제어에 관한 실험적 연구
김하덕, 곽경민, 배철호 et al. · 1998
An Experimental study was performed to investigate flow characteristic of multi-stage expansion valve applied with inverter heat pump. Multi-stage expansion consists of parallel valve which is controled T type and Ball type of solenoid valve. In minimum load T and Ball type of solenoid closed. In Rated load T type open and Ball type closed. But In Maximum load, T and Ball type of solenoid valve always open. Flow characteristic of parallel valve was measured as a function of upstream pressure and subcooling temperature. As a results parallel expansion device can flow control with minimum, rated and maximum operating condition.