국내 사무소용 건축물에서 「공기식 집열창 시스템」의 적용가능성 평가에 관한 연구

박완규, 이승복 · 한국태양에너지학회 학술대회논문집 · 1998

The objective of this study is to evaluate applicability of Air Flow Window Systems in an office building. For this purpose, two simulation programs were used. First, Climate Consultant 2.0 was used for climatic analysis of Seoul, Korea. Second, DOE-2.1E building energy analysis program was used to analyze seasonal heating/cooling loads and energy performance of air flow window systems. Seasonal heating/cooling loads were analyzed through the sensitivity analysis in a unit space and annual energy performance of the K-building was evaluated for the comparative study of air flow window systems. The results of this study show that: 1) As the air cavity of the G-models (which consist of outer window with double clear glass and inner window with single clear glass) increases, the peak heating load increases and the peak cooling load decreases in a unit space. 2) The A-models (which consist of outer window with tinted or reflected glass and inner window with single clear glass under the same air cavity of 30㎝) outperform the other models (which consist of outer window with clear or low-E glass and inner window with clear, reflected, tinted or low-E glass) in terms of heating/cooling loads. 3) AFW-model which has air flow window systems on the south-west facade outperforms D-model which has normal fenestration with double clear glass in terms of electricity/gas energy requirements.