발전기 권선의 흡습 데이터를 통한 건전성 분석과 진단
Kyung Min Park, 윤정택, 윤병동 et al. · 대한기계학회 춘추학술대회 · 2012
The power generator, one of the most critical components in power plant, has usually time- or usage-based maintenance strategy to avoid serious accidents such as unexpected shutdown. However, these maintenance strategies cannot prevent accidents effectively or bring about considerable waste of remaining useful life, thus resulting in high maintenance cost. Prognostics and health management (PHM) technology has recently been developed to predict potential faults with an aim at minimizing the deficiencies of the maintenance strategies. This paper proposes a new health diagnostic method of power generator windings against moisture absorption with a Mahalanobis distance. This health indicator extracted from moisture absorption data shows the health degradation of power generator windings by water leakage. A supervised health classification rule is also suggested by modeling the Mahalanobis distance in a probabilistic manner. This study is demonstrated with 42 windings over three years.
Cited by 0 works.