건식온돌과 이중바닥온돌의 에너지 소비량 비교에 관한 연구

Chang‐Soo Lee, 김난행, 함흥돈 et al. · 대한건축학회 학술발표대회 논문집 - 계획계 · 2005

The purpose of this study is to examine the thermal performance and to evaluate energy consumption of Ondol heating systems. The dry hydronic Ondol and the double floor hydronic Ondol were used for field measurements performed in a residential from January 5 th to February 27 th . In order to validate the results from field measurements, a computer simulation was also performed. Field measurement results indicated that the double floor hydronic Ondol could be effectively used to provide the required indoor temperature and floor surface temperature in a space. Compared to the dry hydronic Ondol, the double floor hydronic Ondol was more effective on energy consumption during intermittent heating period. The energy savings achieved by the double floor hydronic Ondol was 2.9% compared to the dry hydronic Ondol.