흡수식 냉온수기의 불응축가스 추기시스템 개발

김용원, 백영호, 문춘근 et al. · 대한설비공학회 학술발표대회논문집 · 2000

An absorption chiller/heater using LiBr and water as a working fluid is usually designed to get chilled water of 7℃ in summer. In order to get this temperature in the evaporator should retain the pressure as 0.8~0.9㎪. However, by some reasons, if non-absorbable gas inside the machine increase during the operation, pressure increase gradually and the system will be unstable state. Therefore, purging the non-absorbable gas inside the machine is very important for keeping the stable operating condition and good performance. In this paper a automatic gas purge system is described and experiments is carried out not only with the system itself but also by attaching the system to the absorption chiller/heater. The automatic gas purge system shows satisfying results in keeping the vacuum condition of the absorption chiller/heater. The coefficient of performance in the absorption chiller/heater shows 0.82~0.86.