지역난방시스템에서 부분부하 시 유량공급 특성 분석
김화국, 유미혜, 정창호 et al. · 대한건축학회 학술발표대회 논문집 · 2012
The flow imbalance in the pressure differential control valve occurs when the part load appear in the domestic heating system. In order to solve this problem, the application of the pressure differential control valve was proposed and effectiveness of the application was analyzed. Current system utilizes both of the pressure differential control valve in the variable speed circulating pump and the flow limit valve. However the proposed application uses only pressure differential control valve and the flow balancing effect of two systems was analyzed with Flowmaster V17, dynamic computer simulation for 50% and 25% of the part load.
Cited by 0 works.