제습로터의 최적 회전속도
송귀은, 이대영 · 대한설비공학회 하계학술발표회 논문집 · 2007
In this theoretical study, optimum speed of desiccant rotor is investigated with analytic solution of heat and mass transfer models in the rotor through three linearization assumptions. The linearization assumed that temperature variation within the rotor is linear along the length, temperature-humidity ratio relation is linear in a proper range in a psychrometric chart, and relative humidity-sorption capacity relation of the desiccant is linear. Four assumptions causes the non-linear governing equations to be linear and theoretical study on the complicated design parameters of a cooling system with desiccant rotor guides the optimum operation condition. Optimum rotating speed is determined from four dimensionless parameters, average gradient of relative humidity lines in psychrometric chart, sorption capacity of the rotor, and number of transfer unit. This theoretical prediction dictate the optimal operation condition of desiccant rotor guarantying lowest exit humidity without lengthy and complicated design procedure of computation.
Cited by 0 works.