가스차단기내 아크의 복사에너지 측정에 관한 연구

宋基東, 吳年浩, 鄭鎭敎 et al. · 2007

A special PM - Tube(Photo Multiplier Tube) that is using the photoelectric effect has been designed and manufactured to measure the radiation energy of arc in a gas circuit breaker(GCB). The PM-Tube, LLG(liquid light guides), ND(neutral density) filter, and a model gas circuit breaker have been combined for the reception and the transmission of the light and a simplified synthetic test facility with the arc energy measuring system has been established. In the case of SF? gas pressure 5㎏.f/㎠ and arc length 20㎜, the radiation energy increases with the arc current but it tend to be saturated in the above 20㎄. Under the arc current 20㎄, the total radiation energy has the biggest value around 8㎄ and was not exceeded 40% of the total arc energy.