변압기의 권선변형 검증을 위한 LVI 시험기 개발
조국희, 김광화, 곽희로 · 한국조명·전기설비학회 학술대회논문집 · 2000
The assessment of the condition of a transformer winding which is suspected of having suffered short circuit damage can be difficult. Conventional test such as winding resistance, magnetisation current or insulation resistance will only detect damage if a permanent electrical fault exists. Visual inspection of windings necessitates the removal of oil and in many cases only a very small proportion of the winding can be seen. We describe the characteristic of LVI test system and methods to detect the deformation of windings in the power transformers. As the front rise time of recurrent-surge generator pulse less than 1000ns and the peak value of pulse is about 500V, we have the good results of detecting winding deformation in the LVI test of transformers.
Cited by 0 works.