질소-아르곤 혼합가스의 조성비가 쥴톰슨냉동기의 성능에 미치는 영향
홍용주 · 대한기계학회 춘추학술대회 · 2013
Miniature Joule-Thomson refrigerators have been widely used for rapid cooling of infrared detectors, optoelectronic device, and integrated circuits of microelectronics. Nitrogen (NBP 77.35K) and argon gas (NBP 87.3K) are typically used as the cryogen due to their easy availability, low cost and being able to achieve a relatively low cryogenic temperature. Argon is recognized as the preferred coolant for rapid cooling below 100K, but the refrigerator does not attain the temperature below 87.3K. Mixture of nitrogen and argon exhibit intermediate performance between the two pure gases. Cooldown with a nitrogen-argon mixture is slower and the runtime is shorter than with pure argon. But, a significant benefit of including nitrogen is in the mixture is that the temperature of operation is lowered. In this study, effectiveness-NTU approach was adopted to predict the thermodynamic behaviors of the heat exchanger for the Joule-Thomson refrigerator with the nitrogen-argon mixture. The results show the effects of the mixture composition ratio on the performance of the heat exchanger and refrigerator for the given heat exchanger.
Cited by 0 works.