마이크로가스터빈의 부하에 따른 상용 수소흡장냉동기의 성능 최적화에 관한 연구
김형식, 손화승, 최경식 · 설비공학논문집 · 2005
MHR (Metal Hydride Refrigerator) powered by MGT exhaust gas is investigated to find out the optimum conditions corresponding to MGT operating powers. There are many factors to affect cooling capacity of MHR. In this study, the effect of switching time, flow rate of brine on cooling temperature and capacity is investigated. The present results show (1) hydrogen reaction is saturated with 25 min switching time at 25 ㎾ MGT power, (2) cooling power shows maximum phenomenon with increasing switching time, (3) optimum switching times are 20 minutes for 15㎾ MGT power and 15 minutes for 20, 25㎾ MGT power, (4) according to increasing brine flow rate, cooling capacity shows decrease at 15 ㎾ MGT power and changes little at above 20 ㎾ MGT power.