오염발생원의 위치인식에 의한 환기장치 제어방안

한화택, 한정일, 권용일 · 대한설비공학회 학술발표대회논문집 · 2006

This paper presents a control algorithm of supply and exhaust diffusers by recognizing a contaminant source location. CFD analysis has been conducted to calculate steady state airflow and concentration distributions in a model room, which has two supply and two exhaust openings on the ceiling. Calculations have been performed for five cases out of nine different ventilation modes by combining on/off control of the supply and exhaust openings. Local mean residual life times are obtained and compared at 9 internal points for each ventilation case. Depending on the contaminant source location, the ventilation system is operated at an optimum ventilation mode, which can results in maximum exhaust performance.

Cited by 0 works.