알루미늄 평판다관에서의 증발열전달

김기용, 방광현 · 대한설비공학회 학술발표대회논문집 · 1999

The evaporating heat transfer of R-22 in an extruded aluminum multichannel tubes has been experimentally studied. The experimental apparatus consists mainly of a heat pump refrigerant supply system, the test section of 100㎜ aluminum multichannel tubes, subcooler of liquid refrigerant, preheater for control of refrigerant inlet quality. The heat flux is applied by electric heating wire wound on the outer wall of the test section. A set of five thermocouples are embedded at the wall of the test section to measure the wall temperatures. The pressure drop across the test section is measured using a differential pressure transducer. For a refrigerant mass flux of 184 ㎏/㎡s and 378 ㎏/㎡s the inlet quality is varied from 0.1 to 0.9 and the wall heat flux is varied from 1 ㎾/㎡ to 4 ㎾/㎡. The evaporating heat transfer coefficients in the range of the present study were 150~250 W/mK, which is much lower than that for large-diameter pipe. The hydraulic diameter of the present multichannel tubes is 1.6㎜.