타원형 핀-관 열교환기의 설계변수에 따른 성능특성

이승하, 배경진, 권오경 et al. · 대한설비공학회 2014년도 하계학술발표대회 · 2014

The objective of this paper is to study performance characteristics of an elliptic finned-tube heat exchanger. The performance characteristics of a finned-tube heat exchanger were analyzed according to tube diameter and air inlet flow rate using ANSYS CFX. The overall heat transfer coefficient increased and air side pressure drop decreased with a reduction of the tube diameter. As a results, the elliptic outer diameter of 30×42 mm represented the highest overall heat transfer coefficient and smallest air side pressure drop. Relative error between experiment and analytical results was within 4% in the air side pressure drop and 76-90% in overall heat transfer coefficient.