극한상태에서 열전소자와 히트파이프의 성능특성에 관한 연구

Tae Hyong Kim, 고원빈, 고광수 et al. · 대한설비공학회 2014년도 하계학술발표대회 · 2014

In this study, an experimental investigation was conducted to get a heat exchange method when the heat sink temperature is larger than the heat source's. Thermoelectric devices and heat pipes are combined together as heat exchange module. The developed cooling module was installed to the air stream with series and parallel position with respect to the air flow direction. The heat extraction performance of the cooling module shows 283.2W in case of series allocation and 76.7W in parallel. Also it shows that the heat absorption rate of the module is 66.2W in series allocation and 54.1W in parallel. As results, it is found that the developed heat exchange module could be used at the extreme conditions such as the heat transfer direction is vice verse compare the conventional heat transfer mechanism.

Cited by 0 works.

Authors