전기비저항 탐사와 무수보링을 이용한 국내 필 댐 코어존의 건전성 평가
이상종, 임희대, 박동순 · 2015
Electrical resistivity survey (2D and 3D) were employed for detection of possible weak zone of core zones of three central core earth-rockfill dams in Korea. In the 2D results, the core zones is lower resistivity zone with less than 50~400 ohm·m, and the basement is relatively higher resistivity zone with over 1,000 ohm·m. In the 3D results, especially, the weak zone with under 100 ohm·m was detected spatial distribution area in the dam. We also drilled boreholes to collect soil samples of core zones of each dam. Water was not used during boring, because water for rotary wash boring could cause structural damages in earth dams. We found that the soil samples of core zones from all of the boreholes correspond to CL (USCS), but we also found that the fluidized or water-saturated soil samples were found in lower resistivity zones. Therefore, the electrical resistivity survey and drilling method without water are a quick and efficient method for structural-health evaluation which is detection of possible weak zones in earth core rockfill dams.
Cited by 0 works.