[論文] 비틀림 테이프에 의한 二重管型 熱交換器의 性能에 關한 硏究

김두천, 김철한 · 설비저널 · 1982

Friction losses and heat transfer characteristics were studied experimentally for fully developed tubulent flow in tubes with twisted tape swirl generators. Data were obtained for pitch-to-diameter ratios from8.10 to 25.71 with water under forced convection cooling conditions. The experimental results of this and that of previous swirl flow investigation by Smithberg and Landis were compared. Nusselt number and friction data are combined in a constant pumping power comparision for swirl and straight flow, which indicates that improvement of 2.0 times in the best performance can be obtained with twisted tape-insert tube. A twisted tape-insert tube is recommended in the case of low temperature difference in heat-exchanger.

Cited by 0 works.

Authors

References