덕트내 설치된 사각요철의 단락이 열전달 향상에 미치는 영향
우성제, 권혁진, 조형희 · 대한설비공학회 학술발표대회논문집 · 1998
The rib turbulators attached on the inner walls of rectangular ducts enhance heat/mass transfer remarkably, and diverse conditions have long been investigated such as angle-of-attack, the height of ribs, rib-to-rib pitch and so on. In the present study, the effects of the discrete ribs on heat/mass transfer in a duct were investigated and compared with those of the full ribs. For the two angles-of-attack of 45 and 90 degrees, the two types of discrete ribs were considered. The mass transfer experiments by means of the naphthalene sublimation technique were performed to acquire detailed heat/mass transfer coefficients at the Reynolds number of 30,000. The hydraulic diameter(Dh) is 67.3㎜ and the aspect ratio of the test duct is 2.04 with the ribs of 5㎜ high. The discrete ribs have the distributions of the mass/heat transfer coefficients more complicated and uniform to some degree than the full(or continuous) ribs. As the number of discrete ribs increases, these trends become more apparent. The effects of the discrete ribs on heat/mass transfer enhancement are conspicuous at the angle-of-attack of 90 degrees. Hence, heat/mass transfer coefficients increase 23 percents on the average and the hot spot area adjacent to the downstream face of the ribs become narrow, compared with those of the full rib case.