확관 전후 마이크로핀관 내 증발열전달 실험

전상희, 황윤욱, 윤석호 et al. · 대한설비공학회 학술발표대회논문집 · 2000

Evaporative heat transfer characteristics of R-22 in micro-fin tubes before and after tube-expansion have been investigated. Single-grooved micro-fin tubes with outer diameter of 9.52 ㎜ were used as test sections, and they were uniformly heated by applying direct current to the test tubes. The saturation temperature of refrigerant was calculated from the inlet and outlet refrigerant pressures by using an equation of state. Inner wall temperature was calculated from the outer wall temperature which was measured using T-type thermocouples and thermopiles, accounting for heat generation in the tube and heat conduction through the tube wall. Experiments were conducted at mass flow rates of 20 and 30 ㎏/hr and mass fluxes of 100 and 150 ㎏/㎡s. For these mass flow rates or mass fluxes, evaporation temperature was set at 5 and 15℃ and heat flux was changed from 6 to 11 ㎾/㎡. The evaporative heat transfer coefficient of micro-fin tubes after tube-expansion decreased because of the change of fin shape and the enlargement of inner diameter compared to that before expansion. The evaporative heat transfer coefficient of the micro-fin tube after expansion was 19.9% smaller on the average than that before expansion.

Cited by 0 works.

Authors