오발관을 적용한 웨이브 핀 열교환기의 건표면 특성연구
최병남, 김내현, 이을종 et al. · 대한설비공학회 하계학술발표회 논문집 · 2012
In this study, dry surfaces j and f factors were obtained for pre-coated aluminum fin oval tube heat exchangers. Nine samples having different tube rows(2,3 and 4row) and different fin pitches(2.12, 2.54 and 3.18 mm) were tested. j factor of both dry surfaces decrease as the number of tube row and fin pitch increases. f factor shows the same trend.
Cited by 0 works.