배연탈황설비 덕트쿨러에서의 유동 균일화에 관한 연구

김광추, 배진효, 박만흥 · 대한설비공학회 학술발표대회논문집 · 1998

A flow uniformity in a duct cooler of duct system of FGD(Flue Gas Desulfurization) linking a reheater and a absorber has been investigated in the present study. For this purpose, the flow characteristics according to the geometry of a vertical and horizontal vane in a curved duct of the duct system has been examined with the aid of a numerical simulation. The results indicate that the vertical vane with a little deflection toward a recirculation region makes the flow distribution in the duct cooler more uniform than that without deflection. In addition, the flow uniform factor shows its maximum at the middle section of duct cooler and afterwards declines smoothly for a duct system without the vane.