연구논문 : 하수재이용수의 공급관망에서의 관벽잔류염소감소계수 평가 및 영향인자에 대한 연구

이현동, 박재현, 공명식 et al. · Journal of Korean Society of Water Science and Technology · 2013

The experiments on the pipe wall decay constants of residual chlorine in reclaimed water under laboratory conditions using PVC pipe reactor was conducted. As a result of biofilm formation experiment, it was confirmed that there is a limit to the prevention of biofilm formation in water supply systems with PVC pipe, even though residual chlorine existed in reclaimed water. And it can be verified that biofilm as a major factor affects pipe wall decay constant. Under experimental condition, Kw ranged from 0.012 m/day to 0.20 m/day. Although the experiments used the same pipe material, Kw differs significantly in accordance with the conditions of water temperature, initial chlorine concentration, and pipe diameter. From the results of the effects of water temperature on wall decay constant, it was confirmed that the increase of water temperature results in the increase of bulk decay and wall decay constant. From the results of the effects of initial chlorine concentration on wall decay reaction, lower initial chlorine concentration showed higher bulk decay and wall decay constant regardless of water temperature and pipe diameter. From the results of wall decay constant according to pipe diameter, the increase of pipe diameter leads to the decrease of wall decay constant.

Cited by 0 works.