Анализ выбора трансформатора собственных нужд с учетом надежности срабатывания защиты при токах короткого замыкания

А М Любицкий, К А Чебанов, Ж Р Кумратова et al. · Современные проблемы науки и образования · 2015

Currently, the choice of auxiliary transformers, process and circuit protection is given a lot of attention. According to the basic normative document FGC UES For substations with AC and rectified control current auxiliary transformers must be connected via a fuse in the area between the inputs of the main low voltage transformer and switch.However, when choosing a high fuse sometimes forget important indication p. 1.4.3 RB: The chain is protected by a fuse if its breaking capacity is selected in accordance with the requirements of this Regulation and is able to disable the smallest possible fault current in this circuit. Here we should note an important point that is said in the document on the minimum breaking current, which is very characteristic indicator is high fuse.A selection of auxiliary transformers also taking into account not only the analysis of the short-circuit voltage values, and currents of idling.