히트펌프 조건시 휜-관 열교환기의 휜 부분의 착상에 관한 연구

윤신혁, 조금남, 하야세 가쿠 · 2009

The present study measured the frost thickness and frost mass on a flat plate to propose the correlation equations for the local and average frost thickness, frost density, and frost mass. Key parameters were the cooling surface temperature, absolute humidity of air, air temperature, and air velocity. A 50% ethylene glycol aqueous solution was applied as a coolant. The present study also measured the local frost thickness on a fin-tube model to compare the predicted values on the fin of the fin-tube model by the correlation equations from the experiments of the flat plate. The empirical correlations under the heat pump condition in the present study might predict more accurately than the other correlations. The proposed correlation for the frost thickness agreed with the measured data within 5%.

Cited by 0 works.

Authors