한랭지(몽골)에 설치된 지열 히트펌프 시스템의 난방 성능 분석

최재호, 민경천, 손병후 · 대한설비공학회 2014년도 하계학술발표대회 · 2014

The aim of this study is to evaluate the heating performance of the geothermal heat pump(GHP) system for a residential building(420 m2) in Ulaanbaatar, Mongolia. In order to demonstrate the feasibility of a sustainable performance of the system, we installed the water-to-water geothermal heat pump with 10 vertical ground heat exchangers and measured operation parameters from October 19, 2013 to March 26, 2014. The results showed that the entering source temperature of brine returning from the ground heat exchangers was in a range of the design target temperature of ?10℃ for heating. For monthly averaged values, the ground heat exchangers extracted heat of 426.57 kWh from the ground. In addition, the GHP system supplied heat of 669.23 kWh to building and consumed power of 242.66 kWh, respectively. Consequently, the average heating SPF of the overall system was evaluated to be 2.76 during heating season.

Cited by 0 works.