실리카겔-물계 흡착식 냉동기에 관한 실험적 연구
권오경, 윤재호, 김종하 · 대한설비공학회 학술발표대회논문집 · 2006
The objectives of this paper are to investigate the performance of silica gel-water adsorption refrigeration system with heat recovery process from the system experiment. This system can be driven by waste heat at near ambient temperature from 60℃ to 90℃. The cooling capacity and coefficient of performance(COP) were measured from various experimental conditions. An experimental results revealed the influence of operating temperatures(hot, cooling and chilled water), water flow rates, and adsorption-desorption cycle times on cooling capacity and COP. Under the standard conditions of 80℃ hot water, 25℃ cooling water, 14℃ chilled water inlet temperatures and 420sec cycle time, a cooling capacity ℃ of 1.14㎾ and a COP for cooling of 0.55 can be achieved.
Cited by 0 works.